0 avis
PQ Decoupling on Grid-Forming Converter Connected to a Distribution Network
Archive ouverte : Communication dans un congrès
International audience. In recent years, several works on grid-forming converters in transmission networks have been performed. Since these high voltage grids are mainly inductive, a natural decoupling exists between active and reactive power controls. This decoupling facilitates the design and the performance of the grid-forming controllers. However, in distribution applications, it is well known that the R/X ratio of the line impedance is substantially higher, preventing the system from a natural decoupling effect. This paper proposes an original solution to decouple the control and gives an application to a low voltage connection of a grid-forming converter.